Your new AutoLab does not need to be installed in a darkroom.
Once the tanks have been sealed, they are completely light-tight. The dimensions of models
ATL-2200/2300 are as follows (models ATL-2400/2500 have the same dimensions except they're
24" taller):

- 45½" Wide
- 20" Deep
- 24" High
- 46" High (with largest drum raised)
Your new AutoLab should be installed near a drain (check your
local codes regarding disposal of photo chemistry), a water supply (the rinse steps
require tempered water), and a dedicated, grounded, GFCI protected 110V electrical
outlet. Please read section 4.2 about water connection before you determine the final
location of the processor.
The AutoLab should be installed on a stable, level surface
capable of supporting at least 150 lbs for models ATL-2200/2300 and 350 lbs for models
ATL-2400/2500. The surface should be waterproof, and higher than the drain (for models
ATL-2200/2300).
The installation location should have enough vertical
clearance for the processor to empty the largest drum - at least 45½" from the base
of the processor for models ATL-2200/2300, 70" for models ATL-2400/2500.
The ATL-2200/2300 can be installed on our special support
table #4221, in a sink, or on any generic work table. JOBO's support table provides a
convenient, comfortable working height for the processor, and has storage space for your
tanks and drums. This support table can be combined with our chemical collecting cart
#4225 which provides additional storage for used chemistry.
Level the processor. It is extremely important the
processor be absolutely level to develop your film and prints properly. Level the
processor on the trough casing as indicated in the following graphic.
Then, check that the drums attached to the processor are
level.

Back to Top
A dedicated, grounded, UL-approved electrical outlet is
required. At least a 10 amp circuit breaker is needed to run the processor. The AutoLab
draws a maximum of 8.7 amps (240V units draw 5.9 amps), so consider the amperage of any
other appliances if you must connect them to the same circuit. It is strongly recommended
that you consult an electrician when deciding what rating of circuit you need.
A ground fault circuit interrupter (GFCI) is strongly
recommended!
DO NOT OPERATE THE AUTOLAB WITHOUT
ELECTRICAL GROUNDING!
Back to Top
The water pressure must be between 15 and 90 p.s.i. (1-6
bar). Pressure less than 15 p.s.i. will result in an unusually long filling time for the
water bath in addition to inadequate rinsing. Water pressure of over 90 p.s.i. may cause
damage to the processor. If the water pressure exceeds 90 p.s.i., we recommend you
purchase a pressure reducer (#61004). The two hoses (#16171) required to operate the
processor are included.
Warning: To avoid the
possibility of water damage from water leaking from the Water Mixing Panel always make
sure the shut-off valves are accessible and that they're turned off when the processor is
not in use.
Back to Top
Your new AutoLab uses two water supply lines, one cold and
the other tempered. The tempered water line should be adjusted to within ± 0.5°C of the
process temperature. To deliver the tempered water JOBO recommends our water mixing panel
(#4189). It has a low-flow mixing valve and a trickle line; both are needed for optimum
results. Also, the water panel is designed with a special valve to allow you to fill the
processor with tempered water to speed the warm-up time before the first run of the day.
If processes are run at temperatures below ambient room
temperature, the temperature of the supplied water must be lower than the processing
temperature. A water chiller should be used if the supplied water is warmer than that
required by the process you intend to run.
Back to Top
Your new AutoLab has two drains: one water bath drain, and
one drain for the rinse and chemical steps and water bath overflow. Included with the
processor is a drain assembly kit (#93017). Attach the drain lines in the following
manner. The drain labeled "B" is for the chemical reclamation area and overflow
protection. The drain labeled "A" is for the water bath.
If the processor is installed on a work table, you must run
the drain hose for the processor to your drain. Consult your local government code
regarding the disposal of photographic chemistry.

Back to Top
The processor continually circulates the water bath to
maintain the processing temperature. Normal fluctuations in room temperature will have no
impact on the processor's ability to maintain the correct temperature (except when running
processes below room temperature, see sec. 3.4). Do not install the processor directly in
the path of a heating or cooling duct.
To prevent heat loss, which may cause temperature
fluctuations, always keep the rear bottle cover in place when using the processor.
Back to Top
If you have any questions, contact us utilizing one of the
following methods:
Equipment or Processing Questions:
- Phone: Customer Service Department (734) 205-9421
e-mail: tech@jobo-usa.com
Repair Questions:
- Phone: Repair Department (734) 205-9420
- e-mail: repair@jobo-usa.com
- Telephone (734) 677-6989
- Fax: (734) 677-6963
-
- Postal address
- P.O. Box 3721, Ann Arbor, MI 48106
- Shipping Address
- 4401 Varsity Drive, Suite D, Ann Arbor, MI 48108
- Electronic mail
- Sales: sales@jobo-usa.com
- Equipment & Processing Questions: tech@jobo-usa.com
Repair Information: repair@jobo-usa.com
- Shipping or Billing Questions: help@jobo-usa.com
Webmaster: webmaster@jobo-usa.com
-
Back to Top